viktorcode 2 hours ago [-]
> We're approaching a point where industry advances are answering many of the objections (the real ones, not the hysterical ones) raised by the anti-data center movement.

AFAIK the main objections are against sharing the electricity bill and tax exemptions in exchange for a paltry amount of jobs created. Does the author classify those as hysterical?

Also, the existence of technologies does not mean the data center next door will use them. For instance, many can run on closed water loops, but prefer not to, because it is cheaper.

fancyfredbot 1 hours ago [-]
This technology is very likely to see widespread adoption because it's much cheaper not to have chillers.

It should genuinely reduce power required for a given amount of compute which is a good thing. Probably still too much power though.

The real solution to the tax exemption issues, as well as to electrical bills, is at the ballot box and not at an Nvidia design meeting.

theptip 46 minutes ago [-]
All this is easily fixable by a government that actually cares. So many commentators (and the markets) freaking out about how DC buildout is going to halt, but when you look at the demands they are easily satisfiable.

If tax exemptions are off the table, DC operators will just bid higher, including paying a lot more in up-front power commitments, or even just paying off the local communities.

The profit margins on compute are ludicrously high for the big guys, they can and will pay a lot more into the local community if that’s what’s needed to get approval in ‘27. Like, Anthropic could pay double per MW and still have plenty of margin on their inference operations.

It’s been a free for all up until now because of the federal government’s “build at all costs” stance, now the blowback has hit, and next the price will be established and the new equilibrium found.

imoverclocked 1 hours ago [-]
This. It goes deeper though. Yes, data centers use a lot of resources but they also enable abuses of power… political as well as energy.

The rush to put data centers up has created situations where construction of entire nuclear plants are in the plans (~10 year horizon) while the short term goal of energy production is diesel based. Anyone want to wager on the odds that the nuclear plants actually get built? The planned energy production is sometimes in the small percentages of a host countries entire carbon budget.

As for political abuses, flock cameras are definitely enabled by large data centers and have been in the middle of a lot of surveillance scandals. Large layoffs by AI as well as AI slop in practically every sector of our society make it even less palatable to spend more on data centers.

It’s not uncommon for me to go shopping and the person at the checkout is bemoaning the computer in front of them. When is the last time you heard someone outside of tech get excited about a new computer? Unless it’s for games or they had none to start with, I find it to be less and less common. Data centers are just an extension of the general malaise we have created as an industry.

helsinkiandrew 5 hours ago [-]
Discussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178

I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan

IndrekR 5 hours ago [-]
Rule of thumb is that 10 degrees difference makes reactions go, and things fail, twice as fast. This is not exact science, but ballpark is about right.
leoedin 4 hours ago [-]
Is a chip cooled with water at 45C necessarily going to be hotter than a chip cooled by air? I imagine the temperature differentials between chip and coolant on a water cooled setup are much better than the differential between chip and airflow on a typical air cooled setup.
arghwhat 4 hours ago [-]
We strictly speaking never do pure air-cooling in this context.

Traditional water-cooling transfers heat to a fluid, which is then moved to a large radiator to be cooled by air.

Traditional "air-cooling" transfers heat to a phase-changing fluid (heat-pipe), which is then moved to a large radiator to be cooled by air.

Only differences are the type of and amount of fluid, as well as the presence of pumps. Phase-change beat using a fluid as a thermal buffer by quite a bit. The benefit of water is that it's easy to provide massive thermal inertia, and the ability to transfer the heat to a far larger external radiator than could be implemented internally with heat-pipes.

landgenoot 5 hours ago [-]
What kind of reactions? What is a typical component that fails do to heat?
magicalhippo 4 hours ago [-]
It stems from the Arrhenius equation[1] for chemical reactions.

Such a relationship also seems to hold for semiconductors, increase the componentoperatingtemperaturewith 10C and you roughly half the component lifetime[2]. However thermal cycling and similar adds additional stress so it's not as simple a relationship as with chemicals.

[1]: https://en.wikipedia.org/wiki/Arrhenius_equation

[2]: https://www.ti.com/lit/an/snva509a/snva509a.pdf

octoberfranklin 5 hours ago [-]
Electromigration in the wiring on a silicon chip.
lazide 4 hours ago [-]
(Almost) everything chemical, which is at some level almost everything.

Electrical resistance also (generally) increases with temperature, which causes non-linear effects.

(More resistance == more heat, which makes more resistance until the magic smoke comes out, which typically causes a short and resistance drops to zero)

There are some very weird exceptions, but if you don’t know what they are, it won’t help you.

labcomputer 4 hours ago [-]

  > Electrical resistance also (generally) increases with temperature, which causes non-linear effects.
For conductors and insulators, yes. But for semiconductors, resistance drops with temperature because more charge carriers are promoted to the conduction band.
lazide 4 hours ago [-]
More leakage current though, which causes increased noise, which usually causes increased power use to compensate - or errors. Or just more ‘waste’ power use directly.

See my comment about how it generally doesn’t actually help you.

Cryocooling semiconductors is a thing for a reason.

luka 4 hours ago [-]
In semiconductors, resistance decreases with an increase in temperature.
andai 5 hours ago [-]
So... good for Nvidia's profits?
dcrazy 4 hours ago [-]
If the MTBF is still longer than the upgrade cycle, it won’t impact profits.
m463 2 hours ago [-]
wow, that makes me think of used cars that last just a bit longer than lease turnover.

(also, 45°C < current global warming number. if we get another 2°C will it become 47°C?)

notatoad 3 hours ago [-]
that's an interesting question... what as the current relationship between the MTBF and the upgrade cycle, and if they're not aligned then what happens to all that old gear?

are datacenters just chucking all their H100 chips in the bin because they're old now?

esterna 11 minutes ago [-]
I would suppose it matters very little as long as 95% of components become obsolete before they fail.
bob1029 4 hours ago [-]
Semiconductors are unique in that higher temperatures are sometimes preferable for certain electrical characteristics.

I would worry more about thermal cycling and temperature gradients across the die. A machine that runs at 100% 24/7/365 tends to be pretty reliable.

hdndjsbbs 4 hours ago [-]
There is a well-known formula, Black's Equation, which computes mean time to failure for chips caused by electromigration. Temperature is absolutely a factor. In industry it is very common to accelerate MTBF testing by increasing ambient temperature in a heating chamber, because you can predictably calculate MTBF at standard operating temps based on testing at elevated temps.

Electromigration is an unavoidable problem that increases at lower process sizes and higher temperatures. Cutting edge chips at high temps will fail faster without sufficient redundancy designed in.

bob1029 4 hours ago [-]
Black's equation is like a spherical cow approximation when you are looking at something that uses HBM and complex assembly techniques.
hdndjsbbs 2 hours ago [-]
You're not gonna complexly assemble your way out of electrons and atoms colliding. Like I said you can trade off surface area to build in redundancy but for a given node size and temperature electro migration is an unavoidable fact.
unrented7977 2 hours ago [-]
Your HBM and complex assembly is, in reality, a bunch of spherical cows glued together. Each individual component has its own MTBF, and when any one of them dies, the whole assembly goes with it.

Complex assembly increases failures, it does not decrease them.

tomaskafka 40 minutes ago [-]
Why would a billion dollar company dependent on how much new GPUs you buy lie about the component lifespan impact?
iamniels 5 hours ago [-]
This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.

I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.

InsidiousWombat 4 hours ago [-]
power/fiber locations matters far more, that's why we aren't seeing all of the datacenters go to alaska
api 5 hours ago [-]
Also reduces energy use and nukes the water objection.
MrBuddyCasino 4 hours ago [-]
Which is bs anyway.
dgellow 3 hours ago [-]
It’s not bullshit, the issues are localized but do exist. Not all water sources are equivalent, not all locations have the same water resources, and there is an impact on local communities.
MisterMunchkin 1 hours ago [-]
Data centres don’t use water anywhere except America. It’s like shitting in your pants and then asking why pants always have shit in them. You don’t have to do it.
tadfisher 3 minutes ago [-]
Two points:

- In other parts of the world, public resistance is backed by collective action. American protests are tame and non-violent, so it's cheaper to ignore them until the next election.

- The tradeoff for closed-loop cooling is power use, e.g. chillers. The physics require that additional energy conversion to produce heat which must be rejected upstream of the DC. The most power-efficient form of rejecting heat is to dump it into water and then into the air via cooling towers. I am willing to bet that a non-zero percentage of generating plants in, say, Europe are cooled via this method, because it is the cheapest way to do it!

swed420 4 hours ago [-]
The water argument always seemed like bs engineered by pro-DC people:

1) Disseminate fake or exaggerated concerns about water

2) Uninformed people include them in their anti-DC arguments

3) Point out the antis are wrong about water, and imply their other concerns should be ignored entirely

aka "motte-and-bailey fallacy" iirc

BurningFrog 37 minutes ago [-]
I really don't think the world work like this.

Has any operation like this ever succeeded, or even been tried?

fastball 3 hours ago [-]
I think this would be called "false-flagging" (instead of motte-and-bailey) if it was actually a secret pro-data-center astroturfing campaign (which I doubt).
swed420 1 hours ago [-]
False flag might pertain to mass deployment of the technique, but the fallacy itself doesn't have limits on deployment scale afaik.

> which I doubt

Regardless of name, it's a time-tested widely deployed technique by the Uniparty to prop up the illusion of democracy while serving capital interests. It'd be weird if they used it for everything except DCs, though I suppose theoretically possible.

https://en.wikipedia.org/wiki/Uniparty

"Sure, you can have your social media to debate the topics of the day, but we're going to seed it with catnip and false dichotomies." - Elites

red75prime 3 hours ago [-]
The other concerns are "Ahhh! DCs use energy! And they are noisy."
swed420 3 hours ago [-]
I've seen subcomponents to the energy concern:

- Grid upgrade costs provoked by building DCs raises utility costs for small-time consumers

- Adding heat to an already overheating planet

Noise seems like a valid complaint if the area is used to peace and quiet.

There's also a lingering anxiety about mass unemployment, since at this stage almost everybody knows someone who's been laid off and struggles to find work among an increasing pool of unemployed people. Talk of massive DC expansions from AI while the job loss topic is ignored makes for poor optics.

dgellow 3 hours ago [-]
Which are perfectly valid concerns for local residents
MrBuddyCasino 4 hours ago [-]
No it was simply an op along political lines, same as the Huang ouster btw.
jayd16 2 hours ago [-]
You're going to have to explain this considering his ousting and return were under the same administration, same board...
swed420 4 hours ago [-]
It being an op along political lines need not be mutually exclusive. What I described would be part of that op.
GMoromisato 2 hours ago [-]
This also makes orbital datacenters more economical since radiators can be smaller at higher temperatures.
marginalia_nu 1 hours ago [-]
Shouldn't matter very for this application. In space you're using blackbody radiation to get rid of excess heat, and that only does meaningful work if you use a heat exchanger first to increase the temperature of the medium on the radiator side (basically same principle as a refrigerator) since the Stefan–Boltzmann law says thermal radiation per area is P∝T^4 (and blackbody radiation is itself pretty anemic unless temperatures are pretty high).

Also worth noting that only the projected area matters for blackbody radiation so having a convoluted high surface area low volume radiator like we do when air or liquid cooling basically does bupkis.

postalrat 18 minutes ago [-]
I feel the way we get space data centers is to create processing blocks as large as the silicon solar cells. With data moving one way across multiple meters as it is processed.
emil-lp 1 hours ago [-]
More economical than what?
shepherdjerred 1 hours ago [-]
More economical than previous orbital data center concepts
__MatrixMan__ 5 hours ago [-]
That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.
andai 5 hours ago [-]
In Eastern Europe there's a lot of places that get hot water thru underground pipes from a power plant.

Obviously has downsides though, one time they were renovating and we didn't have hot water for a few weeks.

lucaspiller 5 hours ago [-]
My city has district heating which covers around 500k people. The peak output of all the heat plants combined is 239 MW, which is around the same heat output as one or two large data centres.

There are no power plants in my city, so to generate the heat there are heat plants which burn natural gas, biomass or (if supplies get low) something similar to bunker fuel.

Of course it's seasonal, but I'm sure the cost of getting rid of the excess heat in summer would outweigh the current costs of the system (it's more expensive per kWh than a gas boiler), as well as the environmental benefits from not burning all this stuff near where people live.

TeMPOraL 4 hours ago [-]
Demand for hot water would be more consistent throughout the year if not for changes to washing machines and detergents that make it possible to do laundry with absurdly cold water (20 degrees) - which I believe is what makes "fast fashion" possible (the stuff would likely melt apart after few rounds in 60 degrees).
gambiting 4 hours ago [-]
I'm not sure I follow - washing machines heat their own water and only take in cold, how does that change the demand for hot water from the network?
amoshebb 4 hours ago [-]
In America washing machines have two hoses, one for hot (and typically no internal heater at all) and dish washers typically take in hot water too.
wafflemaker 3 hours ago [-]
Which is why you can improve efficiency of your American dishwasher by running hot water for a minute (until it gets hot) before you start it.
toomuchtodo 3 hours ago [-]
Point of use heaters at the inlet are also an option if you’re already installing one at the sink. Think 120V 15-20A resistance heat to heat the water when use starts until hot water from the hot water heater arrives. Is it better or worse than a recirculating pump? Depends, have to model each way.
Scoundreller 2 hours ago [-]
I’ve lived in a building where the recirc prematurely caused leaks on the pex hot water return lines on every riser.

Fun times!

toomuchtodo 1 hours ago [-]
There are people who swear by pex, and as a hobbyist enthusiast in the building science domain, I remain wildly allergic to it versus copper (regardless of the cost and labor premium).

It’s fine if it’s located in an area entirely accessible for the lifetime of the structure for when failure and replacement might occur, but otherwise, it’s pain waiting to fail imho.

Alas, the cost of longtermism mindset (“This is the last time someone will need to touch what I’ve built for the next 100 years, at a minimum”).

gambiting 4 hours ago [-]
TIL!
2 hours ago [-]
omnimus 2 hours ago [-]
Burning trash can be pretty harmless if done properly. In EU it usually is done propelry because of regulations.
__MatrixMan__ 2 hours ago [-]
I doubt the practice will persist if the future forces us to take carbon capture seriously. Whatever energy you get from burning the trash you're gonna have to spend on whatever scheme pulls the carbon from the air. Leaving it as plastic and burying it cuts out the middleman.
omnimus 2 hours ago [-]
Usually it's for heat only? In some places they burn trash (plastic) for heat generation.
yxhuvud 5 hours ago [-]
Not for distribution, as it needs to be hot enough to kill legionalla.
adrianN 2 hours ago [-]
Transfer the heat and upgrade it with a heat pump
teiferer 4 hours ago [-]
District heating is typically a closed loop high pressure system which is not just pute water but has some nasty additives. You then use a heat exchanger in your basement to heat up your hot water coming out of the tap.

Besides, 45C is what needs to go into the data center. What comes out of it is much hotter and you then need to bring it down to 45C. For example by heating your house or your shower water.

deadbabe 5 hours ago [-]
People do not want to bathe in your unethical cursed water that was used to cool chips creating AI content trained on stolen data!
teiferer 4 hours ago [-]
Not sure if sarcastic or not ..

Alternative is to evaporate the water. Not sure how that is more ethical.

As an ethically inclined meat eater (i.e. non-vegetarian) I often prefer eating the parts of the animal that are considered "waste". Sausages (full of things like intestines, liver etc), skewers with chicken hearts, that kind of stuff. Similar to the hot water, at least you can do sth meaningful with the "waste". Arguably more ethical than throwing it away (into which I count biogas generation).

konschubert 4 hours ago [-]
Many parts of the world have abundant rain or sea water, evaporating it should be just fine.
dachris 5 hours ago [-]
There was a satire in Germany many years ago where someone sold a filter that would filter out electricity from nuclear power plants.

Business opportunity: sell a device that restores the water's pureness by mining bitcoin into your account.

__MatrixMan__ 2 hours ago [-]
It's called a heat exchanger. Or is the energy itself cursed?
deadbabe 2 hours ago [-]
A thought experiment, imagine a powerplant that was powered entirely by the forced labor of enslaved people who receive no compensation for their work spinning up energy for the powerplant. Would you use that energy? To heat your home, to cook your food, to power your electronics? Bad energy.

With these heat exchangers, its exactly the same.

__MatrixMan__ 55 minutes ago [-]
If you're morally outraged by something, you're probably better off actively interfering with its operation. Like... get off your high horse and go free the slaves, violently if necessary.

Coming up with ways of accounting for which quanta of energy is bad and which are good as an elaborate way of having washed your hands of the situation is not going to achieve anything.

margalabargala 5 hours ago [-]
At least one atom that has passed through your body, also passed through Hitler. You're already tainted.
throw0101c 4 hours ago [-]
ASHRAE TC 9.9, "Mission Critical Facilities", members are IT folks, and they have defined a Category/Class "A4" that have dry-bulb operating temperatures in the 5-45˚C range:

* https://www.upsite.com/blog/the-importance-of-mutual-underst...

There's also:

> For those familiar with the liquid cooling guidelines, the most obvious change will be that of the Liquid Cooling class designations. Previously, the classes were designated W1, W2, W3, W4 and W5. Each of those classes had a lower temperature limit of 2°C, while the upper limits were 17°C, 27°C, 32°C, 45°C, and Over 45°C respectively. The deficiency in the original designations didn’t really appear until the debate began over adding a class between 32°C and 45°C.

> […] In the end, due to the need for enhanced flexibility, not to mention making it easier for users to remember what temperature goes with the Class, the 5th Edition redesignated the classes based on their upper temperature limit – therefore the classes are now W17, W27, W32, NEW class W40, W45, and the now named W+.

* https://www.upsite.com/blog/what-you-need-to-know-about-ashr...

So >35C isn't entirely unknown already.

* https://www.ashrae.org/technical-resources/bookstore/datacom...

* https://greencalculus.com/standards/ashrae-tc-9-9-thermal-gu...

leni536 3 hours ago [-]
I assume this also means more water moved for the same power and target die temperature. I wonder what other engineering considerations follow from that.
Waterluvian 3 hours ago [-]
Are there any Factorio-like games that treat heat gradients as a kind of spatial resource? Like in some sci fi factory you’ve got an iron smelter pressed right up against your data refinery?
shepherdjerred 1 hours ago [-]
Factorio has this mechanic in the endgame of its Space Age expansion

https://wiki.factorio.com/Aquilo#:~:text=to%20pave%20ice.-,F...

There's also a similar mechanic for nuclear reactors

CivilR 3 hours ago [-]
Oxygen Not Included has a lot of heat management but it's more of a colony sim.
tjbrock 3 hours ago [-]
Second this. One of my favorite games and it has such crazy complexity with heat management and everything else
yread 6 hours ago [-]
Datacenters here on Earth will be much less of a problem with less water consumption because they won't need evaporative cooling
2 hours ago [-]
mschuster91 5 hours ago [-]
Evaporative cooling seems to be some American nonsense.

Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].

For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.

[1] https://www.br.de/nachrichten/bayern/noch-haeufig-ungenutzte...

[2] https://www.bayern-innovativ.de/emagazin/detail/tu-muenchen-...

maeln 5 hours ago [-]
> Evaporative cooling seems to be some American nonsense.

Don't quote me on that, but I remember OVH proudly advertising their new "passive" DC cooling system, which was based on evaporative cooling. The idea of using less energy, but more water was sold as "green" a few years back.

A lot of the new DC getting out of the ground in China where also designed with evaporative cooling in mind. It's definitely not an "american nonsense". What is non sensed though is that both China and the U.S are building a lot of their DC designed with evaporative cooling in water stressed region right now. While it makes sense in terms of cooling (drier air makes evaporative cooling better), I don't think I have to mention the obvious problem of pumping tons of water in dry region.

hommelix 3 hours ago [-]
How I remember the passive cooling of OVH, it was only air. The building ventilation shaft was made with larger opening for fresh air at the bottom and a smaller section chimney at the top. The draft due to the hot air speeding at the chimney pulls the cold air at the bottom.

Unfortunately at the Strasbourg DC, there was no flaps to close the air inlet during fire and this lead to the event that turned a few servers into ash.

adrianN 2 hours ago [-]
Whether water usage is a problem or not entirely depends on the local climate.
entrope 5 hours ago [-]
Some European data centers use evaporative cooling because they got permits long ago, they don't have the physical space for a non-evaporative system, or both. [1] and [2] (both Dutch, because I happened to go there for spring break this year and saw the coverage then) are two examples.

[1]- https://www.techzine.nl/nieuws/infrastructure/577227/datacen... [2]- https://www.nrc.nl/nieuws/2026/08/16/nieuw-amerikaans-datace...

citrin_ru 3 hours ago [-]
> Evaporative cooling seems to be some American nonsense

Evaporative cooling saves energy (compare to A/C like systems with a compressor) so if water is abundant (in some climates it is) it makes sense.

m4rtink 5 hours ago [-]
It's not just modern stuff - steel works and other heavy industry used process powered district heating for a very long time. In some cases it created problems when the enterprise went bankrupt or fragmented and suddenly the process that is providing the district heating might no longer be running. :P
coryrc 1 hours ago [-]
In much of America, you can cheaply stop other people developing their own property by claiming it affects the environment. Here in Seattle, the local labor unions are blocking a grocery store from opening, in a building which used to be a grocery store, by claiming the environmental impact of parking has not been sufficiently measured: https://www.seattletimes.com/business/retail/who-doesnt-want...

So if anyone anywhere just doesn't want data centers, they'll throw every claim and go with whatever sticks.

Oddly, the few immediate claims, like impact from sound levels, they won't support actually writing laws preventing it, because it only affects dozens of people and the rest can't be bothered because it might reduce their leverage in stopping the project, so the immediate neighbors end up getting screwed when projects do get approved...

howard941 3 hours ago [-]
America has a long history of using in-room swamp coolers to endure summer. They don't work well in humid climates of course.
InsidiousWombat 4 hours ago [-]
Its effect of density. Average datacenter takes far less power than one filled to brim with GPUs. They just don't want to spend extra on area for coolers
nekusar 5 hours ago [-]
[flagged]
maeln 5 hours ago [-]
> When water evaporates, where does it go?

> 1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)

> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

Problem is, as far as I know, DC do not use rain / river / aquifer water straight up. Water needs to be processed, and processing water is not free. So you use a significant amount of energy to process water who will be just dumped to release heat.

The other thing is, where the water is coming from and where it goes is very important. A lot of DC in China and the U.S right now are being built in drought prone regions. When you evaporate the water, there is no guarantee that it will rain in the same region. So you are draining the aquifer of already water-stressed region, to have it dumped as rain somewhere else that might not have water stress.

coredog64 4 hours ago [-]
The Palo Verde Nuclear Generating Station uses residential gray water as it's feed source for evaporative cooling. If toilet water can manage several gigawatts of nuclear generation, it'll be fine for cooling racks of Blackwell GPUs.
eminence32 5 hours ago [-]
Obviously the water isn't destroyed, but the problem is when you pull water out of some deep aquifer. It make take a Very Long Time before that rain can refill the aquifer. Assuming it falls in the right place and not 1000 miles away.

Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.

adrian_b 5 hours ago [-]
Frequently, the water that goes into clouds from some place will not return through rain in the same place.

If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.

Only for datacenters built in rainy places it does not matter whether they evaporate water.

coredog64 4 hours ago [-]
So like Oregon along a river, Loudoun County in Virginia, or central Ohio? One might almost think that the datacenter operators take this into account.

https://www.ncei.noaa.gov/access/monitoring/climate-at-a-gla...

https://www.currentresults.com/Weather/Ohio/average-yearly-p...

mschuster91 5 hours ago [-]
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.

But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.

Friends don't let friends run evaporative cooling if there is literally any other way.

nekusar 5 hours ago [-]
You make a good point. The current USA push for datacenters is more a game of how much they can externalize the costs to everyone else, and internalize all the gains.

Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.

The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".

And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".

swiftcoder 4 hours ago [-]
> And no, data centers do not need drinkable water for the compute

A bunch of datacentres run on water that is significantly purer than plain old drinking water - they sometimes need a pre-treatment step to purify the incoming utility water. Apparently all those tasty dissolved solids can wreak havoc in a cooling loop...

dextrous 3 hours ago [-]
Excellent Buggles lyric reference as the lead-in, thank you! I always post another line in these cases

“I met your children. What did you tell them?”

quickthrowman 5 hours ago [-]
Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.

1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling

Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.

https://mitchellt.com/2018/10/23/why-is-55-so-important.html

The same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)

ExoticPearTree 5 hours ago [-]
ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).

The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.

Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.

As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.

jeffwass 4 hours ago [-]
What fraction of a typical data center’s power usage comes from the chillers?
KaiserPro 4 hours ago [-]
Depends on the datacentre.

for "traditional" datacenters, its up to half. Ie you put in one megawatt and then spend a megawatt to move that heat outside. (although its never quite that bad, you need to spec it for the hottest day in that area + 10%)

If you use evaporative cooling, then you cut your cooling bill significantly (ie top up chillers plus cooling loop pumps)

latchkey 4 hours ago [-]
tomaskafka 42 minutes ago [-]
Excellent, hyperscalers don’t need to care about climate anymore as ability to work in 45 degrees Celsius means AI will comfortably keep working through human extinction level temperatures just fine.

Shareholders in climatized New Zealand bunkers rejoice.

imp0cat 20 minutes ago [-]
Also various forms of fungi. Fun times ahead! https://time.com/article/2026/10/27/why-dangerous-fungi-are-...
mvc 1 hours ago [-]
Glad the computers will continue to be operable when their rampant use makes planet hotter. Are us humans going to get a similar upgrade?
jfkimmes 4 hours ago [-]
Wow, this contains so many AI-isms that it is legitimately hard to read for me. Shocking to see such blatant slop in a journalistic publication (vs. a random blog post).

https://www.pangram.com/history/6901a6ab-fc82-40bc-9be6-f67a...

origini 4 hours ago [-]
I don't get it anyway.

These DC are big and create a lot of heat. Why is there nothing around them which would take that heat off them?

Can't we even use a heatpump to even take it to make a higher difference for some industries etc.?

Suckerburg even destroyed a CPU based DC to build it up again as a GPU based on. They can build stuff

dist-epoch 2 hours ago [-]
Sahara land suddenly becoming very valuable.
FLeXMurphy 4 hours ago [-]
We haven't noticed it because we've literally been doing this for decades in non-data-center applications. Holy marketing batmans.
cucumber3732842 6 hours ago [-]
Sooooo... downsize everything, still run chillers and have better capex for the same-ish opex?

There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.

samuelknight 5 hours ago [-]
No. Similar capex and better opex. Chillers are not very expensive compared to the chips. Data center economics is built around PUE, a ratio of total power / IT power. The optimal data center has PUE=1, a real data center is >1 because some power has to go to facilities and cooling.
InsidiousWombat 4 hours ago [-]
Google's fleet wide PUE is around 1.1
lokar 6 hours ago [-]
Sure, it expands to space of workable trade offs. Some times that will mean no chillers.
5 hours ago [-]
hinkley 3 hours ago [-]
[dead]
arjendevos 2 hours ago [-]
[dead]
LoganDark 3 hours ago [-]
[dead]
ZiiS 5 hours ago [-]
I know it is irrational but factual documentaries like the matrix do make me think if we should optimize machines to need body temperature fluids.
5 hours ago [-]
Guidelines | FAQ | Lists | API | Security | Legal | Apply to YC | Contact
Rendered at 20:41:56 GMT+0000 (Coordinated Universal Time) with Vercel.